An open-loop transfer function for pointing control of a two-inertia satellite is shown below. The output of the transfer function is the measured pointing angle of the satellite, and the input is the control voltage for a DC servo motor which produces the torque needed to rotate the satellite. The closed-loop system is stable with closed-loop poles at s = -0.0199+/-j0.0688, -0.0840+/-j0.9876, -10.0004.
Uncompensated System Root Locus
Specifications for the system are: (1) steady-state error for a ramp input = 0.2; (2) settling time for a step input of approximately 40 seconds.
The given system is Type 1. The velocity error constant for the given system
is 0.1276, so the steady-state error for a ramp input is 7.84. Therefore,
the compensator must reduce the steady-state by a factor of about 40 to
satisfy the error specification. The step response is too slow, so the
dominant closed-loop poles must be moved to the left.
Uncompensated System Step Response
To achieve the settling time and steady-state error specifications, a two-step procedure will be used. First, a phase lead compensator will be designed to move the dominant branches of the root locus to satisfy the settling time specification. Second, a phase lag compensator will be designed to reduce the steady-state error to the required value.
To achieve a settling time of 40 seconds for the step response, the real
part of the dominant closed-loop poles should be at approximately s = -0.1.
The ratio of the imaginary part of the dominant pole to the real part will
affect the percent overshoot. Although no specification is given on
overshoot in this problem, the point s = s1 = -0.1 + j0.1 is chosen. The
root locus must be made to go through this point, and then this point must
be made a closed-loop pole.
Exploded View of Uncompensated Root Locus
The phase angle of the given satellite model at the selected point s1 is 104.9 degrees. Therefore, for s1 to be on the root locus, the compensator must have an angle of +75.1 degrees at the point s1. The compensator zero must add more than this amount since the compensator pole will subtract its phase angle from that of the zero. The zero is placed directly below the chosen point, zc_lead = -0.1. The choice of location for the compensator zero is somewhat arbitrary -- the normal rule of thumb would place it at or to the left of the plant pole at s = -0.04 (so that the chosen point s1 will represent a dominant closed-loop pole) and yet provide an angle greater than 75.1 degrees at s1. With the chosen zero location, the angle from the zero to s1 is 90 degrees, so the compensator pole must provide an angle of 14.9 degrees at s1. The distance to the left of s1 for the pole to give that angle is 0.376; therefore, the compensator pole is located at s = -0.476. The lead compensator's gain must make the magnitude of the given system in series with the lead compensator equal to 1 at the point s1. The magnitude at that point is 0.0799, so the lead compensator gain is 12.5101. The closed-loop poles are at s = -0.1+/-j0.1, -0.3402, -0.0721+/-j0.9599, -10.0003. This system is stable and satisfies the settling time specification.
Lead Compensated System Root Locus
Lead Compensated System Root Locus -- Exploded
View
Lead Compensated Step Response
The purpose of the lag compensator is to increase the effective gain at the point s = s1 without changing the root locus at that point or changing the dominance of that point. The ratio of compensator zero to pole is the amount by which the error must be reduced. The lead-compensated system has a velocity error constant Kv = 0.335, so the steady-state error is 2.985. The lag compensator must reduce that by a factor of 14.9248 in order to meet the specification. The value of alfa for the lag compensator is equal to 14.9248. The compensator zero is chosen to the right of the point s1 by a factor of 100, and the pole is to the right of that by the factor of alfa. Their locations are s = -0.001 and s = -6.7003e-05, respectively. The closed-loop poles are located at s = -0.10028e-03, -0.0992+/-j0.1004, -0.3408, -0.0721+/-j0.9599, -10.0000. The velocity error constant of the system is now 5, so the steady-state error specification is satisfied, and the step response is virtually unchanged from the lead-compensated response. The effect of the closed-loop pole at s=-0.10028e-03 is almost cancelled by the compensator zero at s = -0.001, and the other closed-loop poles are very close to their previous locations. The point s1 is no longer a closed-loop pole, but the movement of that pole is negligible.
Lag-Lead Compensated Root Locus -- Exploded
Once
Lag-Lead Compensated Root Locus -- Exploded
Twice
Lag-Lead Compensated Step Response
The steady-state ramp error for the given system is approximately 8 and for
the lead-compensated system it is approximately 3. Both of those systems
are in steady-state long before the final lag-lead-compensated. For the lag-lead compensated system,
the settling time in the ramp response is long due to the
very low frequency pole. It takes several thousand seconds for the
lag-lead compensated system to reach steady state.
Original, Intermediate, and Final Ramp Responses
Circuit models for implementing compensators such as these as electronic
circuits can be found in the text Modern Control Engineering, 3rd
Edition, by Ogata, Prentice Hall, 1997.
The model for this example was adapted from an example
in Feedback Control of Dynamic Systems, 2nd Edition, by G.F.
Franklin, J.D. Powell, and A. Emami-Naeini, Addison-Wesley, 1991 using
certain numerical values from the Hubble Space Telescope.
Click the icon to return to the Dr. Beale's home page
Lastest revision on
Friday, May 26, 2006 9:19 PM